Central Maine Diesel Inc. (“CMD”) is not affiliated with, sponsored by or otherwise associated with American Honda Motor Company, Inc. (“American Honda”). We purchase genuine Honda® engines and assemble generator sets. CMD’s Propane/Natural Gas and Triple-Fuel System (options) are not approved by American Honda. Honda® is a registered trademark of American Honda.
Slow Speed 10,000 Watt Generator - This brand new slow-turning generator (longer life, better fuel economy!) is suitable for standby or continous use and has plenty of power to your home, job site or business. This unit features a 24 HP Honda X 670 V-Twin engine and with its slow speed design has lower sound levels, better fuel economy and longer service life then the competition. This unit features a critical-type exhaust silencer, brushless generator head (maintenance-free!), electric start, full pressure lubrication, heavy-duty dual element air cleaner, oil cooler, steel skid base w/ vibration isolators for low noise and vibration and a sound level of only 73 dB(A). LP Gas, Natural Gas and Tri-Fuel conversions are available.
Model Number
04592
Electrical Specifications
-
Power Single-Phase
---
Automatic Voltage Regulation
Standard
Is this unit suitable for powering sensitive electronic equipment like a laptop computer?
Yes
Maximum Output
10,500 watts
Continous Output
10,000 watts
Load Amperage at 120 volts
---
Maximum Load
87.5 Amps
Continous Load
83.3 Amps
Load Amperage at 240 volts
---
Maximum Load
43.75 Amps
Continous Load
41.7 Amps
Sound Level @ 23 ft(7 m) at full load
73 dB(A)
Model Number
04592
Engine
-
Model
Honda GX 670
Type
V-Twin
Horsepower
24
Oil Capacity (w/ Oil Filter)
2.01 qts.
Cylinders
2
Cylinder Block
Cast Iron Cylinder Bore
Bore & Stroke
3.0" x 2.8"
Exhaust Outlet
1" OD Muffler Outlet
Low Oil Alert
Standard
Air Cleaner
Heavy-Duty Dual Element
Charging System
12 V - 20 Amp
Cooling
Air-Cooled
Fuel
Gasoline (LP Gas, Natural Gas is Optional)
Starting System
Electric
Model Number
04592
Consumption
-
Consumption at 1/2 load
0.90 gallons/hour
Consumption at 3/4 load
1.08 gallons/hour
Consumption at full load load
1.24 gallons/hour
Scroll Down to View More
Model Number
Control Panel
1. Key-Start Panel
2. Oil Filler Cap
3. Air Filter
4. Muffler
5. 3/8" FNPT Fuel Fitting
6. Generator
7. Generator Output Cover
8. Control Panel
Model Number
04592
Installation Data
-
Fuel Inlet Hose Size
3/8"
Fuel Fitting
3/8" FNPT
Fuel Inlet Pressure
LP Gas: 11-14" Water Column Natural Gas: 5-7" Water Column
Minimum Power Lead Size
0-50 Feet: 6 AWG 51-100 Feet: No. 4 AWG
No. Power Lead Conductors
4
Exhaust Outlet
1" OD Muffler Outlet
Battery Type
12 VDC - 400 CCA
Engine Oil Type
10W-30 Synthetic
Exhaust Location & Direction (Facing Engine)
Left-side
Service Points (Facing Engine)
Oil Fill Cap: Left-Side Oil Filter: Left-Side Fuel Inlet: Right-Side Power Output: Back-Side Control Panel: Back-Side Air Filter: Front-Side